[Uimp] rated impulse withstand voltage | 0.5 kV |
[Us] rated supply voltage | 12/24 V DC, voltage limits: 8...33 V |
Adjustable range of switching point on falling pressure | 1.2...24.2 bar |
Adjustable range of switching point on rising pressure | 2...25 bar |
Ambient air temperature for operation | -15...85 °C |
Ambient air temperature for storage | -40...85 °C |
Controlled fluid | Fresh water (0...125 °C) Hydraulic oil (-15...125 °C) Corrosive fluid (-15...125 °C) Air (-15...125 °C) |
Current consumption | < 4 mA |
Destruction pressure | 62.5 bar |
Diameter | 22.8 mm |
Discrete output type | Solid state PNP, 1 NC |
Drift of the sensitivity | +/- 0.015 % of measuring range/°C |
Drift of the zero point | +/- 0.015 % of measuring range/°C |
Electrical circuit type | Control circuit |
Electrical connection | 3 pins 1 male connector M12 |
Fluid connection type | G 1/4A (male) conforming to ISO 228 |
Height | 72 mm |
IP degree of protection | IP67 conforming to EN/IEC 60529 IP66 conforming to EN/IEC 60529 |
Local display | Without |
Materials in contact with fluid | Ceramic FPM PPS Stainless steel type AISI 303 |
Maximum permissible accidental pressure | 56 bar |
Maximum switching current | 150 mA |
Measurement accuracy | +/- 1 % of the measuring range |
Mechanical durability | >= 10000000 cycles |
NEMA degree of protection | NEMA 4 |
Operating position | Any position |
Possible differential maximum at high setting | 23.8 bar |
Possible differential minimum at high setting | 0.75 bar |
Possible differential minimum at low setting | 0.75 bar |
Pressure sensor name | XMLG |
Pressure sensor size | 25 bar |
Pressure sensor type | Electronic pressure sensor |
Product certifications | CSA UL |
Product or component type | Electronic pressure sensors |
Product weight | 0.095 kg |
Protection type | Load short-circuit Reverse polarity |
Protective treatment | TC |
Quantity per set | Set of 25 |
Range of product | OsiSense XM |
Repeat accuracy | +/- 0.1 % of the measuring range |
Resistance to conducted disturbances, induced by radio frequency fields | 30 V (0.15...80 Hz) conforming to EN/IEC 61000-4-6 |
Resistance to electromagnetic fields | 200 V/m (80...1000 Hz) conforming to EN/IEC 61000-4-3 |
Resistance to electrostatic discharge | 8 kV (on contact) conforming to EN/IEC 61000-4-2 15 kV (in air) conforming to EN/IEC 61000-4-2 |
Resistance to fast transients | 4 kV conforming to EN/IEC 61000-4-4 |
Resistance to magnetic fields | 30 A/m (50 Hz) conforming to EN/IEC 61000-4-8 |
Response time on output | < 2 ms |
RoHS (date code: YYWW) | Compliant - since 0627 - Schneider Electric declaration of conformity |
Setting | Factory setting |
Shock resistance | 25 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Standards | CE EN 50081-1 EN 50082-2 EN 61000-6-2 EN/IEC 60947-1 EN/IEC 60947-5-1 |
Surge withstand | 500 kV (12 Ohm) conforming to EN/IEC 61000-4-5 1 kV (42 Ohm) conforming to EN/IEC 61000-4-5 |
Sustainable offer status | Not Green Premium product |
Type of output signal | Discrete |
Type of packing | Group |
Vibration resistance | 20 gn (f = 9...2000 Hz) conforming to EN/IEC 60028-2-6 |