[Uimp] rated impulse withstand voltage | 0.5 kV DC |
[Us] rated supply voltage | 24 V DC SELV, voltage limits: 17...33 V |
Ambient air temperature for operation | -20...80 °C |
Ambient air temperature for storage | -40...80 °C |
Analogue output function | 4...20 mA |
Controlled fluid | Refrigeration fluid (-20...80 °C) Hydraulic oil (-20...80 °C) Air (-20...80 °C) Fresh water (0...80 °C) |
Current consumption | <= 50 mA |
Delay first up | <= 300 ms |
Depth | 42 mm |
Destruction pressure | 7.5 bar 109 psi 750 kPa |
Device short name | XMLR |
Display accuracy | <= 1 % of the measuring range |
Display response time type | Slow 600 ms Normal 200 ms Fast 50 ms |
Display type | 4 digits 7 segments |
Drift of the sensitivity | +/- 0.03 % of measuring range/°C |
Drift of the zero point | +/- 0.1 % of measuring range/°C |
Electrical connection | 4 pins M12 male connector |
Fluid connection type | G 1/4 (female) conforming to DIN 3852-Y |
Front material | Polyester |
Height | 93 mm |
Housing material | Polyacrylamide 316L stainless steel |
Hysteresis on analogue output | <= 0.2 % of the measuring range |
IP degree of protection | IP67 conforming to EN/IEC 60529 IP65 conforming to EN/IEC 60529 |
Linearity error on analogue output | <= 0.5 % of the measuring range |
Marking | CE |
Materials in contact with fluid | Ceramic Fluorocarbon FKM (Viton) 316L stainless steel |
Electromagnetic compatibility | Electrostatic discharge immunity test - test level 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2 Electrical fast transient/burst immunity test - test level 2 kV conforming to EN/IEC 61000-4-4 Surge immunity test - test level 1 kV conforming to EN/ |
Maximum permissible accidental pressure | 7.5 bar 109 psi 750 kPa |
Measurement accuracy on switching output | <= 0.6 % of the measuring range |
Mechanical durability | >= 10000000 cycles |
Operating position | Any position, but disposals can falsified the measurement in case of upside down mounting |
Overall accuracy | <= 1 % of the measuring range |
Pressure sensor size | 1 bar 14.5 psi 100 kPa |
Pressure switch type of operation | Pressure transmitter |
Product certifications | CULus |
Product or component type | Electronic pressure sensors |
Product weight | 0.19 kg |
Protection type | Overload protection Overvoltage protection Reverse polarity Short-circuit protection |
Range of product | OsiSense XM |
REACh | Reference not containing SVHC above the threshold |
Repeat accuracy | <= 0.2 % of the measuring range |
Response time on output | <= 10 ms for analog output |
RoHS (date code: YYWW) | Compliant - since 1351 - Schneider Electric declaration of conformity |
Shock resistance | 50 gn conforming to EN/IEC 60068-2-27 |
Standards | UL 61010-1 EN/IEC 61326-2-3 |
Sustainable offer status | Not Green Premium product |
Type of output signal | Analog |
Vibration resistance | 20 gn (f = 10...2000 Hz) conforming to EN/IEC 60068-2-6 |
Width | 41 mm |