Navigér
Sœg

Pressostat med display 100Bar 24V 4-20mA+NPN


Varenr:XMLR100M1N25
El nr:7524600947
EAN13 nr:3389119611275
Pakning:1stk

[Uimp] rated impulse withstand voltage0.5 kV DC
[Us] rated supply voltage24 V DC SELV, voltage limits: 17...33 V
Adjustable range of switching point on falling pressure5...97 bar 72.5...1407 psi 0.5...9.7 MPa
Adjustable range of switching point on rising pressure8...100 bar 116...1450 psi 0.8...10 MPa
Ambient air temperature for operation-20...80 °C
Ambient air temperature for storage-40...80 °C
Analogue output function4...20 mA
Controlled fluidRefrigeration fluid (-20...80 °C) Hydraulic oil (-20...80 °C) Air (-20...80 °C) Fresh water (0...80 °C)
Current consumption<= 50 mA
Delay first up<= 300 ms
Depth42 mm
Destruction pressure600 bar 8700 psi 60 MPa
Device short nameXMLR
Discrete output typeSolid state NPN, NO/NC programmable
Display accuracy<= 1 % of the measuring range
Display response time typeSlow 600 ms Normal 200 ms Fast 50 ms
Display type4 digits 7 segments
Drift of the sensitivity+/- 0.03 % of measuring range/°C
Drift of the zero point+/- 0.1 % of measuring range/°C
Electrical connection4 pins M12 male connector
Electromagnetic compatibilityElectrostatic discharge immunity test - test level 8 kV air, 4 kV contact conforming to EN/IEC 61000-4-2 Electrical fast transient/burst immunity test - test level 2 kV conforming to EN/IEC 61000-4-4 Surge immunity test - test level 1 kV conforming to EN/
Fluid connection typeG 1/4 (female) conforming to DIN 3852-Y
Front materialPolyester
Height88 mm
Housing materialPolyacrylamide 316L stainless steel
Hysteresis on analogue output<= 0.2 % of the measuring range
IP degree of protectionIP67 conforming to EN/IEC 60529 IP65 conforming to EN/IEC 60529
Linearity error on analogue output<= 0.5 % of the measuring range
Local signalling1 LED yellow for light ON when switch is actuated
MarkingCE
Materials in contact with fluid316L stainless steel
Maximum permissible accidental pressure300 bar 4350 psi 30 MPa
Maximum switching current250 mA
Measurement accuracy on switching output<= 0.6 % of the measuring range
Mechanical durability>= 10000000 cycles
Minimum differential travel3 bar 43.5 psi 0.3 MPa
Operating positionAny position, but disposals can falsified the measurement in case of upside down mounting
Overall accuracy<= 1 % of the measuring range
Pressure sensor size100 bar 1450 psi 10 MPa
Pressure switch type of operationPressure transmitter with 1 switching output
Product certificationsCULus
Product or component typeElectronic pressure sensors
Product weight0.186 kg
Protection typeOverload protection Overvoltage protection Reverse polarity Short-circuit protection
Range of productOsiSense XM
REAChReference not containing SVHC above the threshold
Repeat accuracy<= 0.2 % of the measuring range
Response time on output<= 5 ms for discrete output <= 10 ms for analog output
RoHS (date code: YYWW)Compliant - since 1351 -  Schneider Electric declaration of conformity
Shock resistance50 gn conforming to EN/IEC 60068-2-27
StandardsUL 61010-1 EN/IEC 61326-2-3
Sustainable offer statusNot Green Premium product
Switching output time delay0...50 s in steps of 1 second
Type of output signalAnalogue + discrete
Vibration resistance20 gn (f = 10...2000 Hz) conforming to EN/IEC 60068-2-6
Voltage drop<= 2 V
Width41 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info