Navigér
Sœg

pressure sensor XMP - 6 bar - G 1/4 hun - 3 NC - without control type


Varenr: XMPA06C2141
Produktet findes ikke i SAP!

[Ui] rated insulation voltage500 V conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage6 kV conforming to EN/IEC 60947-1
Adjustable range of switching point on falling pressure0.2...4.8 bar
Adjustment range high setting1...6 bar
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
Cable entry2 entries incorporating Pg 13.5 plastic cable gland, cable outer diameter: 9...13 mm conforming to NF C 68-300
Class of protection against electric shockClass I conforming to IEC 60536
Contacts type and composition3 NC snap action
Control typeWithout
Controlled fluidSea water (0...70 °C) Fresh water (0...70 °C) Air (0...70 °C)
Depth98 mm
Destruction pressure30 bar
Electrical circuit typePower circuit
Electrical connectionScrew-clamp terminals, clamping capacity: minimum : 2 x 4 mm²
Electrical durability700000 cycles (2.2 kW, operating rate: 10 cyc/mn, load factor: 0.4, 400 V AC 3 phases) 600000 cycles (1.5 kW, operating rate: 10 cyc/mn, load factor: 0.4, 230 V AC 3 phases) 500000 cycles (3 kW, operating rate: 10 cyc/mn, load factor: 0.4, 400 V AC 3 phas
Enclosure materialPA impregnated with fibreglass
Fluid connection typeG 1/4 (female) conforming to ISO 228
Height106 mm
IP degree of protectionIP54 conforming to EN/IEC 60529
Local displayWithout
Materials in contact with fluidCanvas covered nitrile Chromated zinc alloy
Mechanical durability1000000 cycles
Operating positionAny position
Operating rate10 cyc/mn
Possible differential maximum at high setting4.2 bar
Possible differential minimum at high setting1.2 bar
Possible differential minimum at low setting0.8 bar
Pressure actuatorDiaphragm
Pressure sensor nameXMP
Pressure sensor size6 bar
Pressure sensor typeElectromechanical pressure sensor
Pressure switch type of operationRegulation between 2 thresholds
Product end of life instructionsNeed no specific recycling operations
Product environmental profileAvailable Download Product environmental
Product specific application-
Range of productOsiSense XM
REAChReference not containing SVHC above the threshold
Repeat accuracy< 3.5 %
Resistance across terminals<= 25 MOhm conforming to NF C 93-050 method A <= 25 MOhm conforming to IEC 60255-7 category 3
RoHS (date code: YYWW)Compliant - since 0627 -  Schneider Electric declaration of conformity
Sale per indivisible quantity1
Scale typeAdjustable differential
SettingNut
Shock resistance50 gn conforming to IEC 60068-2-27
StandardsCE EN/IEC 60947-4-1
Sustainable offer statusGreen Premium product
Terminal block type6 terminals
Terminals description ISO n°1(1-2)NC (3-4)NC (5-6)NC
Type of decompression valveWithout
Vibration resistance3 gn (f = 10...500 Hz) conforming to IEC 60068-2-6
Width57 mm

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info