Navigér
Sœg

Fotoelektrisk sensor - XUX - modtager - Sn 40m - 24..240 V AC/DC - terminaler


Varenr:XUX2ARCNT16R
El nr:7524804400
EAN13 nr:3389110170436
Pakning:1stk

[Sn] nominal sensing distance40 m thru beam need a transmitter XUX0ARCTT16T
[Us] rated supply voltage24...240 V AC/DC
Add on outputWithout
Ambient air temperature for operation-25...55 °C
Ambient air temperature for storage-40...70 °C
Cable entry1 entry for M16 x 1.5 cable gland, cable outer diameter: 7...10 mm
Delay first up< 60 ms
Delay recovery< 25 ms
Delay response< 25 ms
Depth77 mm
Detection systemThru beam
Discrete output function1 NC + 1 NO
Electrical connectionScrew-clamp terminals, 1 x 1.5 mm² or 1 x 0.75 mm² with adaptor
Electrical durability500000 cycles, cos f = 1, 3000 cyc/mn, relayoutput(s) 500000 cycles, cos f = 0.4, 500 cyc/mn, relayoutput(s)
Electronic sensor typePhoto-electric sensor receiver
EmissionInfrared thru beam
Enclosure materialPBT
Height92 mm
IP degree of protectionIP67 double insulation conforming to IEC 60529 IP65 double insulation conforming to IEC 60529
Lens materialPMMA
MaterialPlastic
Maximum sensing distance60 m thru beam
Output typeRelay
Power consumption in W2 W AC/DC
Product certificationsCE CSA UL
Product end of life instructionsAvailable Download End of life manual
Product environmental profileAvailable Download Product environmental
Product specific application-
Product weight0.2 kg
Range of productOsiSense XU
REAChReference not containing SVHC above the threshold
RoHSCompliant - since 0914 -  Schneider Electric declaration of conformity
Sensor designCompact 92 x 71
Sensor nameXUX
Series nameGeneral purpose single mode
Setting-upSensitivity adjustment
Shock resistance30 gn (duration = 11 ms) conforming to IEC 60068-2-27
Status LED1 LED (green) for supply 1 LED (yellow) for output state
Supply circuit typeAC/DC
Supply voltage limits20...264 V AC/DC
Sustainable offer statusGreen Premium product
Switching capacity in mA3 A (cos ? = 1 for 0.5 million cycles at 1 operating cycle per second at 250 V) 0.5 A (cos ? = 0.4 for 0.5 million cycles at 1 operating cycle per second at 250 V)
Switching frequency<= 20 Hz
Type of output signalDiscrete
Vibration resistance7 gn, amplitude = +/- 1.5 mm (f = 10...55 Hz) conforming to IEC 60068-2-6
Voltage drop<= 1.5 V (closed state)
Width31 mm
Wiring technique5-wire

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025

Katalog

Hjem Info