Trepositionshĺndtag med knap 2+1N/O+1N/C

Varenr: | XY2AU2 |
El nr: | 7517148652 |
EAN13 nr: | 3389110362015 |
Pakning: | 1stk |
 |
[Ithe] conventional enclosed thermal current | 5 A |
[Ui] rated insulation voltage | 250 V outside (degree of pollution: 3) conforming to IEC 60947-1 250 V inside (degree of pollution: 2) conforming to IEC 60947-1 125 V on supplementary contact |
[Uimp] rated impulse withstand voltage | 2.5 kV conforming to EN 60947-1 |
Ambient air temperature for operation | -10...60 °C |
Ambient air temperature for storage | -40...70 °C |
Cable entry | 1 entry, 7...13 mm |
Class of protection against electric shock | Class II conforming to EN/IEC 61140 |
Component name | XY2AU |
Connections - terminals | Terminal block : 1 x 0.34...1 x 1.5 mm˛ |
Contact code designation | R300 with DC-13 utilisation category at 250 V, 0.1 A DC current conforming to IEC 60947-5-1 appendix A R300 with DC-13 utilisation category at 125 V, 0.22 A DC current conforming to IEC 60947-5-1 appendix A C300 with AC-15 utilisation category at 250 V, 1 |
Contacts operation | Slow-break |
Contacts type and composition | 2 NO + 1 NC |
Enclosure material | PA66 |
Enclosure type | Double insulated |
IK degree of protection | IK06 conforming to EN 50102 |
Installed device | 1 NO additional contact |
IP degree of protection | IP65 conforming to IEC 60529 |
Mechanical durability | 1000000 cycles |
Operating force | 12 N 50 N |
Operator position information | 3 positions |
Positive opening | With conforming to IEC 60947-5-1 appendix K |
Product or component type | Enabling switch |
Product weight | 0.32 kg |
Protective treatment | TC |
Range of product | Preventa XY2 |
Shock resistance | 10 gn for 11 ms conforming to IEC 60068-2-27 |
Short circuit protection | 4 A fuse protection by cartridge fuse type gG |
Standards | CULus 508 EN/IEC 60947-1 EN/IEC 60947-5-1 CSA C22.2 No 14 |
Vibration resistance | 6 gn (f = 5...55 Hz) conforming to IEC 60068-2-6 |
Yderliger oplysninger:
Se venligst SE katalog©Schneider Electric A/S 2025