[Ie] rated operational current | 0.27 A at 250 V DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A 3 A at 240 V AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A |
[Ithe] conventional enclosed thermal current | 10 A |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 400 V, degree of pollution 3 conforming to EN/IEC 60947-1 300 V conforming to UL 508 |
[Uimp] rated impulse withstand voltage | 4 kV |
Ambient air temperature for operation | -20...60 °C |
Ambient air temperature for storage | -40...70 °C |
Auxiliary contacts operation | Slow-break |
Cable entry number | 2 plain hole with blanking plug 1 tapped entry (ISO M20) for cable gland |
Class of protection against electric shock | Class I conforming to NF C 20-030 Class I conforming to EN/IEC 61140 |
Connections - terminals | Screw clamp terminal, clamping capacity: 1 x 0.5...2 x 1.5 mm² |
Contacts type and composition | 2 NC |
Depth | 105 mm |
Device short name | XY2CE |
Distance between cable supports | 10 m |
Dust zone | Zone 21 - 22 |
Height | 142 mm |
Housing colour | Red RAL 3000 |
IP degree of protection | IP65 |
Key number | 421 |
Local signalling | Without pilot light |
Marking | II2 D-Ex tb IIIC T85°C Db IP65 |
Mechanical durability | 10000 cycles |
Number of cables | 1 |
Positive opening | With, conforming to EN/IEC 60947-5-1 section 3 |
Product certifications | INERIS 04ATEX0015 |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product or component type | Latching emergency stop trip wire switch |
Protective treatment | TC |
Range of product | Preventa XY2 |
Reset | By key-release pushbutton |
Resistance across terminals | <= 25 MOhm conforming to NF C 93-050 method A <= 25 MOhm conforming to EN/IEC 60255-7 category 3 |
RoHS (date code: YYWW) | Compliant - since 0852 - Schneider Electric declaration of conformity |
Safety level | Can reach SIL 3 conforming to EN/IEC 61508 Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1 Can reach PL = e with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849- |
Safety reliability data | B10d = 50000 value given for a life time of 20 years limited by mechanical or contact wear |
Shock resistance | 50 gn for 11 ms conforming to EN/IEC 60068-2-27 |
Short circuit protection | 10 A cartridge fuse type gG conforming to EN/IEC 60269 |
Standards | ATEX D 94/9/CE EN/IEC 60079-0 EN/IEC 60079-31 |
Sustainable offer status | Not Green Premium product |
Tightening torque | 0.8...1.2 N.m |
Trigger cable anchor point | LH side |
Trigger cable maximum length | 70 m |
Vibration resistance | 10 gn (10...300 Hz) conforming to EN/IEC 60068-2-6 |