Navigér
Sœg

Wirenĝdstop 30m 2NC+1NO M20


Varenr:XY2CJR19H29
El nr:7524677909
EAN13 nr:3389119619486
Pakning:1stk

[Ie] rated operational current1.5 A at 240 V AC-15, B300 conforming to EN/IEC 60947-5-1 appendix A 0.1 A at 250 V DC-13, R300 conforming to EN/IEC 60947-5-1 appendix A
[Ithe] conventional enclosed thermal current6 A
[Ui] rated insulation voltage300 V (degree of pollution: conforming to CSA C22.2 No 14 300 V (degree of pollution: conforming to UL 508 400 V (degree of pollution: 3) conforming to EN/IEC 60947-1
[Uimp] rated impulse withstand voltage4 kV conforming to EN/IEC 60947-1
Ambient air temperature for operation-25...70 °C
Ambient air temperature for storage-40...70 °C
Body materialZamak
Cable entry number1 tapped entry for ISO M20 cable gland
Connections - terminalsScrew clamp terminal 1 x 0.34...2 x 0.75 mm² Screw clamp terminal 1 x 0.34...1 x 1 mm²
Contacts operationSlow-break
Contacts type and composition2 NC + 1 NO
Cover materialGalvanised steel
Device short nameXY2C
Distance between cable supports5 m
Housing colourRed RAL 3000
IP degree of protectionIP67 for conforming to IEC 60529 IP66 for conforming to IEC 60529
Local signallingColor indicator
MarkingCE
Mechanical durability100000 cycles
Number of cables1
Overvoltage categoryClass I conforming to EN/IEC 61140
Positive openingWith conforming to EN/IEC 60947-5-1
Product certificationsCCC for CSA for UL for category NISD emergency stop devices
Product or component typeLatching emergency stop rope pull switch
Product weight0.669 kg
Protective treatmentTC
Range of productPreventa XY2
ResetBy pull button
Resistance across terminals<= 25 MOhm conforming to NF C 93-050 method A <= 25 MOhm conforming to EN/IEC 60255-7 category 3
Safety levelCan reach SIL 3 with the appropriate monitoring system and correctly wired conforming to EN/IEC 61508 Can reach category 4 with the appropriate monitoring system and correctly wired conforming to EN/ISO 13849-1 Can reach PL = e with the appropriate monito
Safety reliability dataB10d = 500000 with value given for a life time of 20 years limited by mechanical or contact wear conforming to IEC 60947-5-5
Shock resistance50 gn for 11 ms conforming to EN/IEC 60068-2-27
Short circuit protection6 A by gG cartridge fuse conforming to EN/IEC 60269
StandardsEN/IEC 60204-1 EN/IEC 60947-5-1 EN/IEC 60947-5-5 EN/ISO 13850 UL 508 Machinery directive 2006/42/EC CSA C22.2 No 14 Work equipment directive 2009/104/EC
Terminals description ISO n°1(13-14)NO (21-22)NC (31-32)NC
Tightening torque0.8...1.2 N.m
Trigger cable anchor pointRH side
Trigger cable maximum length30 m
Vibration resistance10 gn (f = 10...150 Hz) conforming to EN/IEC 60068-2-6

Yderliger oplysninger: Se venligst SE katalog









©Schneider Electric A/S 2025