[Ie] rated operational current | 0.27 A at 250 V, DC-13, Q300 conforming to EN/IEC 60947-5-1 appendix A 3 A at 240 V, AC-15, A300 conforming to EN/IEC 60947-5-1 appendix A |
[Ithe] conventional enclosed thermal current | 10 A |
[Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 6 kV conforming to IEC 60664 |
Ambient air temperature for operation | -25...70 °C for standard environment |
Ambient air temperature for storage | -40...70 °C |
[Ui] rated insulation voltage | 300 V conforming to CSA C22.2 No 14 contact block 500 V degree of pollution 3 conforming to IEC 60947-1 contact block 50 V conforming to IEC 60947-1 indicator light module 300 V conforming to UL 508 contact block |
Associated head | ZCKE05 ZCKE06 ZCKE08 ZCKE21 ZCKE23 ZCKE61 ZCKE619 ZCKE62 ZCKE629 ZCKE63 ZCKE64 ZCKE65 ZCKE66 ZCKE67 |
Body material | Metal |
Body type | Fixed |
Cable entry | 1 entry tapped for M20 x 1.5 cable gland |
Contacts material | Silver plated contacts |
Contacts operation | Slow-break, break before make |
Contacts type and composition | 1 NC + 1 NO |
Depth | 44 mm |
Device short name | ZCKJ |
Electrical circuit type | Indicator light module 2 LED DC, 24 V (20...30 V) service life: 100000 h with reverse polarity protection |
Electrical connection | Screw-clamp terminals, clamping capacity: 1 x 0.5...2 x 2.5 mm² |
Electrical durability | 5000000 cycles, DC-13 48 V, 9 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC-13 24 V, 13 W, operating rate: < 60 cyc/mn, load factor: 0.5 conforming to IEC 60947-5-1 appendix C 5000000 cycles, DC |
Environmental characteristic | Standard environment |
Height | 77 mm |
IK degree of protection | IK08 |
IP degree of protection | IP65 |
Local display | With |
Minimum actuation speed | 6 m/min |
Number of poles | 2 |
Number of steps | 1 1 position |
Positive opening | With |
Product compatibility | XCKJ |
Product end of life instructions | Need no specific recycling operations |
Product environmental profile | Available Download Product environmental |
Product or component type | Limit switch body |
Product weight | 0.32 kg |
Range of product | OsiSense XC |
REACh | Reference not containing SVHC above the threshold |
Resistance across terminals | 0.25 mOhm conforming to IEC 60255-7 category 3 |
RoHS (date code: YYWW) | Compliant - since 1103 - Schneider Electric declaration of conformity |
Series name | Standard format |
Short circuit protection | 10 A by gG cartridge fuse |
Sustainable offer status | Green Premium product |
Width | 40 mm |